Network Management Card
– User Manual 34003991EN/EC Page 78/118
7.1.3 Technical characteristics
Functions Parameters Default values Possible values
JBUS/MODBUS
communication
- Baud rate
- Parity
- Slave number
- 9600 bauds
- without parity
- Slave nr 1
- 1200, 2400, 4800, 9600
- Without parity, even parity
- 1 to FF (hexadecimal)
RS232 link
- Link connection in
transmit
data (Tx) or receive data
(Rx)
- Rx on pin 1
- Tx on pin 3
- Rx on pin 1
- Tx on pin 3
RS485 link - Termination - No termination - With or without (2 or 4
wires)