Network Management Card
– User Manual 34003991EN/EC Page 67/118
5.1.1.3 Shutdown when backup time is less than
When the Network Management Card detects that the percentage of backup time remaining is less than the value set,
the shutdown sequence is started.
5.1.1.4 Shutdown duration
Duration (in seconds) required for the system protected by the protection application to shut down.
The protection application transmit their own "Shutdown duration" to the Network Management Card.
Based on these values (maximum Shutdown duration of all subscribed customer systems) that the card will send to
the delayed shutdown order to the UPS.